MTP® Fiber Optic Trunks

FMA-12XX

 

        • OM3, OM4, OM5 multimode and OS2 applications
        • 12 and 24-fiber connections
        • 100% factory tested for insertion and return loss
        • Made in the USA with Corning® Clear Curve™ Bend Insensitive fiber glass
        • Designed with USconec MTP Elite® connectors
        • CORE8 & CORE12 configurations specifically designed for 40/100 GbE or 16/32 Gb fiber channel applications
        • Up to 144 Fibers with 12 or 24 sublets
        • Available for the SIGNAMAX 5-day Fiber Program
        • Insertion loss:

      SM/MM Low Loss: Typical 0.10 dB, Max 0.35 dB
      Standard SM: Typical 0.25 dB, Max 0.75 dB
      Standard MM: Typical 0.20 dB, Max 0.60 dB

       

 

  • TRANSMISSION PERFORMANCE

Cable:
OS2 (9/125 μm):
Max. Attenuation [dB/km] 0.5/0.4
OM3 (50/125 μm):
Max. Attenuation [dB/km] 3.5/1.5; Bandwidth [MHz.km] 2,000 @850nm
OM4 (LOMMF):
Max. Attenuation [dB/km] 3.0/1.0; Bandwidth [MHz.km] 4,700 @850nm
OM5 (WBMMF):
Max. Attenuation [dB/km] 2.5/0.8; Bandwidth [MHz.km] 3,500 @500nm
MTP Connector
1Return loss:
Elite® MM MT Ferrule: > 20 dB
Std MM MT Ferrule: > 20 dB
Elite® SM MT Ferrule: > 60 dB (8º Angle Polish)
Std SM MT Ferrule: > 60 dB (8º Angle Polish)
1Insertion loss:
Elite® MM MT Ferrule: 0.10 dB Typical, 0.35 dB Max
Std MM MT Ferrule: 0.20 dB Typical, 0.60 dB Max
Elite® SM MT Ferrule: 0.10 dB Typical, 0.35 dB Max
Std SM MT Ferrule: 0.25 dB Typical, 0.75 dB Max
1. For 48- & 72-fiber MM MTs or 24-fiber SM MTs, performance assumes physical contact on all fibers.

  • MECHANICAL

Connector Ferrule: Ceramic
End-Face Radius of Curvature: 10 mm (0.39 in) < R < 30 mm (1.18 in)
Apex Offset: < 50 μm

  • CONSTRUCTION

Outer Jacket: Flame Retardant PVC
Strength Member: Aramid Yarn
Tight Buffer: Flame Retardant PVC

  • ENVIRONMENTAL CONDITIONS

Operating Temperature: 32 to 158°F (0 to 70°C)
Storage Temperature: -40 to 158°F (-40 to 70°C)
Operating RH: 95% (non-condensing)

  • COMPLIANCE

Tested per: ANSI/EIA-455-171 Method D3 & Method D1, IEC 61280-4-1
ANSI/TIA-568-C.3, ISO/IEC 11801 2nd Ed., IEC 61755-3-31/GRADE B, CENELEC EN 50173, UL94V-0, Flame Rating: NFPA262 (Plenum), UL1666 (Riser), UL1658 (FT4)

  • WARRANTY

5-year Limited Component
10-year Signamax Base Trunk
15-year Signamax Extended Component
25-year Signamax Cabling System

 

 

Download Specifications (PDF 660Kb) Revised 10.2018

 

[AAA]
FIBER COUNT
  [B]
PERFORMANCE
  [EE]
1CONNECTOR 1
  [FF]
1CONNECTOR 2
  [G]
POLARITY
  [JJ]
FAN OUT (IN)
006   S: Standard   T1: 12 MTP Female   T1: 12 MTP Female   A: Type A   xx
008   L: Low Loss   T2: 12 MTP Male   T2: 12 MTP Male   B: Type B  
012       T3: 12 MTP Female/APC   T3: 12 MTP Female/APC   C: Type C   [K]
STAGGERED
016   [C]
FIBER TYPE
  T4: 12 MTP Male/APC   T4: 12 MTP Male/APC       N: None
024   3: OM3   T5: 24 MTP Female   T5: 24 MTP Female   [H]
COLOR
  L: Left
032   4: OM4   T6: 24 MTP Male   T6: 24 MTP Male   T: TIA Standard   R: Right
048   5: OM5   T7: 24 MTP Female/APC   T7: 24 MTP Female/APC   B: Blue    
072   9: OS2   T8: 24 MTP Male/APC   T8: 24 MTP Male/APC   O: Orange   [LLL]
2LENGTH (FT)
096       T9: 8 MTP Female   T9: 8 MTP Female   G: Green   xxx
144   [D]
1JACKET
  T0: 8 MTP Male   T0: 8 MTP Male   W: Brown    
    R: OFNR   U1: 16 MTP Female   U1: 16 MTP Female   R: Red   [M]
DELIVERY
    P: OFNP   U2: 16 MTP Male   U2: 16 MTP Male   K: Black   S: Standard
    L: LSZH   U3: 16 MTP Female/APC   U3: 16 MTP Female/APC   Y: Yellow   E: 5-Day
        U4: 16 MTP Male/APC   U4: 16 MTP Male/APC   V: Violet    

 

PART NUMBER EXAMPLE:

M012S4PT1TAT00N050E – 12 fiber OM4 assembly with a MTP (F) to MTP (F) with Type A polarity with no break;configured to be 50 feet in length and delivered in 5 days.

1. Additional jacket materials & connectors available by request, contact customer service.
2. Pulling eye included on all assemblies over 50 ft in length. Lengths over 100 ft are packaged on reels.
*Need more customization, contact tech support for a consult.

MTP® is a registered trademark of US Conec, Ltd.